OI-6000 CSA #152 Sensor Assembly for Combustible Gas

 

The Otis Instruments OI-6000 Series Ambient Air Combustible Gas Detector is a versatile assembly that uses an infrared sensor element to detect combustible gases in ambient air. The assembly is certified to CSA 22.2 No. 152 and ANSI/ISA 12.13.01-2013 Performance standards for quick response to combustible gas. Wired power (12 to 35 VDC) with 4-20 mA analog and RS-485 Modbus outputs standard. Magnetic switches allow for nonintrusive calibration while in the field as well as full system settings and diagnostics while remaining Class I Division 1 Groups C & D Certified.

Part Number Formula OI-6000-IR-152-X-X-O — No relays installed OI-6000-IR-152-X-R-O — 2 Dry contact relays installed

 

Clear

Description

 

Sensor Type: Infrared Sensor Element

Operating Voltage: Wired Power (3-Wire) 12 to 35 VDC

Current Draw: 1 Amp Maximum

Protection:

  • Power Electromagnetic Interference (EMI) Filter

  • 4-20 mA Surge Suppression

  • RS-485 Surge Suppression

Display Screen:

  • 102×64 Resolution Graphical LCD Screen

  • Transflective (Sunlight Readable) with white LED Backlight

Interface:

  • 3 Push-Buttons (MENU, ADD, and SUB)

  • 3 Magnetic Non-Intrusive Switches for Calibration (MENU, ADD and SUB)

Customizable Settings: 2 Individually-Configurable Alarm LED/Relay Set-Points

Tamb Temperature Range: -40°C to +54°C / -40°F to 130°F

Wired Analog Output:

  • 4-20 mA (3-Wire)

  • Fault Terminal

  • Optional 2 Dry-Contact Relays with Replaceable 4 Amp Fuses

Digital Output: RS-485 Modbus

Remote Mount Control Unit (Optional Additional Feature): OI-6800 Remote Control Unit

  • Allows full operational control of the remotely connected OI-6000-IR-152-X-X-O

  • Available in Explosion Proof and Non-Explosion Proof Enclosure Option

  • Ability to include an additional 2 Dry-Contact Relays

  • Ability to add a GEN II 900 MHz or 2.4 GHz Radio for Wirefree Signal Reporting to other Otis Monitors

Product Dimensions: 5.5″ T x 6″ W x 7″ H (8” W x 17” H Maximum w/ Attachments)

Total Weight: 5.75 lbs.

Hazardous Location Certifications and Approvals:

  • Class I, Division 1, Groups C and D T4

  • Ex d ib IIB T4 Gb

  • Class I, Zone 0, IIB Aex d ib T4 Gb

  • CSA 22.2 No. 152

  • ANSI/ISA 12.13.01-2013

  • Tamb –40°C to +54°C

Hardware Warranty: Limited one year

Sensor Element Warranty: 24 Months, subject to Otis verification of element condition

 

OI-6000-IR-152-X-X-O Data Sheet

OI-6000-IR-152-X-X-O Operation Manual

OI-6000 Certificate 1

OI-6000 Certificate 2

OI-6000 Certificate 3

OI-6000 Certificate 4

OI-6000 Certificate 5

 

Your Details

Let us know how to get back to you.


How can we help?

Feel free to ask a question about the specific product.


Additional information

Relays

None, Two Dry Contact Relays



Featured Products